• Beckhoff EL6022
• Beckhoff Automation
• EtherCAT Terminal
• RS422/RS4
• PLC Module
• SERIAL INTERFACE RS422
• Beckhoff EL6022 EtherCAT RS485
• 2-channel communication interface
The EL6022 serial interface enables the connection of devices with two RS422/RS485 interfaces. The devices connected to the EL6022 EtherCAT Terminal communicate with the automation device via the Coupler. The active communication channel operates independently of the higher-level EtherCAT system in full duplex mode with 300 baud up to 115.2 kbaud. The RS422/RS485 interfaces guarantee high interference immunity through electrically isolated signals. The EL6022 can provide 2 x 5 V/20 mA out of the E-bus supply (electrically isolated, short-circuit proof) for the supply of external devices.
Specification of EL6022 Beckhoff EtherCAT Terminal PLC model:
Connection technology: D-sub, 9-pin
Data transfer channels: 2
Data transfer rates: 300…115,200 baud; default: 9600 baud, 8 data bits, no parity and one stop bit
Interfaces: 2 x RS422/RS485
Line impedance: 120 Ω
Cable length: approx. 1000 m twisted pair
Providing external supply: 2 x max. 5 V/20 mA, out of E-bus supply, short-circuit proof
Power supply: via the E-bus
Electrical isolation: 500 V (E-bus/signal voltage)
Data buffer: 864 bytes receive buffer, 128 bytes transmit buffer
Configuration: no address setting, configuration via the controller
Current consumption E-bus: typ. 270 mA
Special features: 2 x 5 V/20 mA for external supply
Weight: approx. 55 g
Operating/storage temperature: -25…+60°C/-40…+85°C
Relative humidity: 95%, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.: IP20/variable